ADAM-4115-B
6ch RTD Robust Modbus rs485 Remote I/O
SPEDIZIONE GRATUITA
Bisogno di aiuto?
General
Certification: CE, FCC
Connectors: 2 x plug-in terminal blocks (#14 ~ 22 AWG)
Power Consumption: 1.2 W @ 24 VDC
Watchdog Timer: System (1.6 second)
Supported Protocols: ASCII command and Modbus/RTU
Interface: RS-485, Micro USB
RTD Input
Channels: 6 differential
Input Connections: 2, 3-wire
Sampling Rate: 10/100 Hz total channels (selected by utility)
Input Type: Pt, Balco and Ni RTD
RTD Types and Temperature Ranges
Pt 100 RTD:
Pt -50°C to 150°C
Pt 0°C to 100°C
Pt 0°C to 200°C
Pt 0°C to 400°C
Pt -200°C to 200°C
Pt 1000 RTD:
Pt -40°C to 160°C
Balco 500 RTD:
-30°C to 120°C
Ni 50 RTD:
Ni -80°C to 100°C
Ni 508 RTD:
Ni 0°C to 100°C
Accuracy: ±0.1%
Span Drift: ± 25 ppm/°C
Zero Drift: ±6 μV/° C