EDR-120-12
AC-DC DIN rail power supply 120W, input voltage range 90-264VAC, output 12VDC 10A
Bisogno di aiuto?
EDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.
EDR-120 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20℃ and 60℃ under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV EN60950-1, and etc.) make EDR-120 a very competitive power supply solution for industrial applications.
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- EN61000-6-2(EN50082-2) industrial immunity level
- 100% full load burn-in test
- 2 years warranty
Specifications
OUTPUT
DC VOLTAGE: 12V
RATED CURRENT: 10A
CURRENT RANGE: 0 ~ 10A
RATED POWER: 120W
RIPPLE & NOISE (max.): 100mVp-p
VOLTAGE ADJUSTMENT RANGE: 12 ~ 14V
VOLTAGE TOLERANCE: ±2.0%
LINE REGULATION: ±0.5%
LOAD REGULATION: ±1.0%
SETUP, RISE TIME: 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.): 16ms/230VAC 10ms/115VAC at full load
INPUT
VOLTAGE RANGE: 90 ~ 264VAC
FREQUENCY RANGE: 47 ~ 63Hz
EFFICIENCY (Typ.): 85%
AC CURRENT (Typ.): 2.25A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.): 20A/115VAC 35A/230VAC
LEAKAGE CURRENT: <1mA / 240VAC
PROTECTION
OVERLOAD: 105 ~ 130% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE: 14 ~ 17V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE: Shut down o/p voltage, re-power on to recover
ENVIRONMENT
WORKING TEMP.: -20 ~ +60°C (Refer to "Derating Curve")
WORKING HUMIDITY: 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY: -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT: ±0.03%/°C (0 ~ 50°C)
VIBRATION: Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC
SAFETY STANDARDS: Ul508, TUV EN60950-1 approved;(meet EN60204-1)
WITHSTAND VOLTAGE: I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE: I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION: Compliance to EN55032 (CISPR32) Class A, EN61000-3-2,-3
EMC IMMUNITY: Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF: 474.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSIONS: (WxHxD) 40 x 125.2 x 113.5 mm