MGate 5217I-1200-T
2 port Modbus-to-BACnet/IP gateway, 1200 points, 2kV isolation, 12 to 48 VDC, 24 VAC, -40 to 75°C
Certificati
Features and Benefits
- Supports Modbus RTU/ASCII/TCP master/client
- Supports BACnet/IP slave/server
- Supports 600 points and 1200 points models
- Supports COV for fast data communication
- Supports virtual nodes designed to make each Modbus device as a separate BACnet/IP device
- Configures Modbus commands quickly by editing an Excel spreadsheet
- Embedded traffic and diagnostic information for easy troubleshooting
- Built-in Ethernet cascading for easy wiring
- Industrial design with -40 to 75°C operating temperature range
- Serial port with 2 kV isolation protection
- Dual AC/DC power supply
- 5-year warranty
- Security features based on IEC 62443
Introduction
The MGate 5217I Series comprise 2-port BACnet gateways that can convert Modbus RTU/ACSII/TCP to BACnet/IP protocol. Depending on the size and the scale of the network, the gateways provide 600-point and 1200-point models. All models are rugged, DIN-rail mountable, operate in wide temperatures, and offer built-in 2kV isolation for serial signals.
Specifications
Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector):
2
Auto MDI/MDI-X connection
Magnetic Isolation Protection: 1.5 kV (built-in)
Ethernet Software Features
Industrial Protocols: Modbus TCP Client (Master), BACnet/IP Server (Slave)
Configuration Options: Web Console (HTTP/HTTPS), Device Search Utility (DSU), Telnet Console
Management: ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, NTP Client
MIB: RFC1213, RFC1317
Time Management: NTP Client
Serial Interface
No. of Ports: 2
Connector: DB9 male
Serial Standards: RS-232/422/485
Baudrate: 50 bps to 921.6 kbps
Data Bits: 7, 8
Parity: None, Even, Odd, Space, Mark
Stop Bits: 1, 2
Flow Control: RTS Toggle (RS-232 only), RTS/CTS, DTR/DSR
RS-485 Data Direction Control: ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485: 1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485: 120 ohms
Isolation: 2 kV (built-in)
Serial Signals
RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422: Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w: Data+, Data-, GND
RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND