BB-485OP
rs422/485 OPTICAL ISOLATOR REPEATER
Bisogno di aiuto?
FEATURES
- 2 kV optical isolation protection
- Add up to 32 nodes to RS-485 network
- RS-422 2-wire, RS-485 2 or 4-wire
- Modbus support
- UL Recognized
Introduction
Model 485OP is an optically isolated RS-422/485 signal repeater. In addition to 2KV isolation on the data lines, it can be used to extend RS-422/485 circuits an additional 1.2 km (4,000 ft.), thereby doubling the range. An added benefit is the ability to add another 32 nodes to an RS-485 network and join 2 and 4 wire systems.
The compact design fits almost anywhere. Terminal blocks allow easy installation. Wiring schematic on the label eliminates guesswork. A 12 VDC power supply is included with blades for US, EU, UK, AU, UP & CN.
SPECIFICATIONS
SERIAL PROTOCOLS
RS-422 4-wire
RS-485 2-wire
RS-485 4-wire
ISOLATION
Lines Protected: Data lines
Method: Optical
Rating: 2000 V
SURGE SUPPRESSION
Lines Protected: Data lines
Method: TVS
Rating: 6.5V bi-directional
600W peak power dissipation
INDUSTRIAL BUS
Modbus ASCII/RTU
POWER
Connector: Terminal block
Voltage: 10 to 14 VDC
Power Consumption: 1.0 W
Source: Included wall transformer or other 12 VDC source
POWER SUPPLY
Input Voltage: 96 - 264 VAC
Input Connections: AC blades for US, EU, UK, AU, CN & JP
Output Connections: Stripped & tinned leads
Output Current: 500 mA
Output Power: 6W
Efficiency Level: VI
Ouput Voltage: 12 VDC
TERMINAL BLOCKS
Wire Size: 22 to 14 AWG
Torque: 0.5 Nm
LED INDICATORS
2 x Data (Red): Flashes when data received
ENCLOSURE
Material: Plastic
IP Rating: 30
Dimensions: 9.7 x 6.1 x 2.5 cm (3.8 x 2.4 x 1.0 in)
Mounting: In line
ENVIRONMENTAL
Operating Temperature: 0 to 55 °C (32 to 131 °F)
Operating Humidity: 0 to 95% non-condensing
MTBF: 453103 hours
MTBF Calculation Method: Parts Count Reliability Prediction