IMC-101G
Industrial 10/100/1000BaseT(X) to 1000BaseSX/LX/LHX/ZX media converter, 0 to 60°C
Bisogno di aiuto?
Prodotti Correlati
Certificati
Features and Benefits
- 10/100/1000BaseT(X) and 1000BaseSFP slot supported
- Link Fault Pass-through (LFP)
- Power failure, port break alarm by relay output
- Redundant power input
- -40 to 75°C operating temperature range (T models)
- Designed for hazardous locations (Class 1 Div. 2/Zone 2, IECEx)
- More than 20 options available
Introduction
The IMC-101G industrial gigabit modular media converters are designed to provide reliable and stable 10/100/1000BaseT(X) to 1000BaseSX/LX/LHX/ZX media conversion in harsh industrial environments. The IMC-101G’s industrial design is excellent for keeping your industrial automation applications running continuously, and each IMC-101G converter comes with a relay output warning alarm to help prevent damage and loss. All IMC-101G models are subjected to a 100% burn-in test, and are available in models that support a standard operating temperature range of 0 to 60°C, and an extended operating temperature range of -40 to 75°C.
Technology
Standards:
IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X) and 100BaseFX
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3z for 1000BaseSX/LSX/LX/LH/LHX/ZX/E2X
Interface
Fiber Ports: 1000BaseSFP slot
LED Indicators: PWR1, PWR2, FAULT, 10/100M (TP port), 1000M (TP and Fiber port)
DIP Switches: Port break alarm mask, Link Fault Pass-through, SFP Auto/Force
Alarm Contact: One relay output with current carrying capacity of 1 A @ 24 VDC
RJ45 Ports: 10/100/1000BaseT(X)
Optical Fiber
Note: See the SFP-1G series.
Physical Characteristics
Housing: Metal, IP30 protection
Dimensions: 53.6 x 135 x 105 mm (2.11 x 5.32 x 4.13 in)
Weight: 630 g
Installation: DIN-Rail mounting, wall mounting (with optional kit)
Environmental Limits
Operating Temperature:
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Power Requirements
Input Voltage: 12 to 45 VDC redundant inputs
Input Current: 110 mA @ 24 VDC
Connection: Removable terminal block
Overload Current Protection: 2.5 A
Reverse Polarity Protection: Present
Standards and Certifications
Safety: UL 508
Hazardous Location: UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2 Ex nC nL IIC T4, IECEx
EMC: CE, FCC
EMI: FCC Part 15 Subpart B Class A, EN 55022 Class A
EMS:
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 3,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8,
EN 61000-4-11
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Green Product: RoHS, CRoHS, WEEE
MTBF (mean time between failures)
Time: 500,540 hrs
Database: Telcordia (Bellcore), GB
Warranty
Warranty Period: 5 years