TDR-240-24
AC-DC Slim Three Phase Industrial DIN Rail power supply 240W, output 24VDC 10A, input voltage range 340-550VAC, with PFC Function, 63mm slim width
Bisogno di aiuto?
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
Features
- Three-Phase 340 ~ 550Vac wide range input (Dual phase operation possible)
- 63mm slim width
- Built-in passive PFC function compliance to EN61000-3-2
- High efficiency 92% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Full power between -30~+60°C
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL61010(industrial control equipment)approved
- EN61000-6-2(EN50082-2) industrial immunity level
- DC OK relay contact
- 3 years warranty
SPECIFICATIONS
OUTPUT
DC VOLTAGE: 24V
RATED CURRENT: 10A
CURRENT RANGE: 0 ~ 10A
RATED POWER: 240W
RIPPLE & NOISE (max.): 100mVp-p
VOLTAGE ADJUSTMENT RANGE: 24 ~ 28V
VOLTAGE TOLERANCE: ±1.0%
LINE REGULATION: ±0.5%
LOAD REGULATION: ±1.0%
SETUP, RISE TIME: 2000ms, 60ms/400VAC 1500ms, 60ms/500VAC at full load
HOLD UP TIME (Typ.): 20ms / 400VAC 40ms / 500VAC at full load
INPUT
VOLTAGE RANGE: Three-Phase 340 ~ 550VAC
FREQUENCY RANGE: 47 ~ 63Hz
POWER FACTOR (Typ.): PF ≧ 0.53/400VAC PF ≧ 0.52/500VAC at full load
EFFICIENCY (Typ.): 92%
AC CURRENT (Typ.): 0.69A/400VAC 0.6A/500VAC
INRUSH CURRENT (Typ.): COLD START 50A
LEAKAGE CURRENT: <2mA / 530VAC
PROTECTION
OVERLOAD: 105 ~ 130% rated output power
Protection type: Constant current limiting, unit will hiccup after 3 sec.
OVER VOLTAGE: 30 ~ 36V
Protection type: Hiccup mode, recovers automatically after fault condition is removed.
OVER TEMPERATURE: Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
DC OK REALY CONTACT RATINGS (max.): 60VDC/0.3A, 30VDC/1A, 30VAC/0.5A resistive load
ENVIRONMENT
WORKING TEMP.: -30 ~ +70°C (Refer to "Derating Curve")
WORKING HUMIDITY: 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY: -40 ~ +85°C, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT: ±0.05%/°C (0 ~ 60°C)
VIBRATION: Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE: 5000 meters
OVER VOLTAGE CATEGORY: Ⅲ;According to EN61558, EN50178,EN60664-1, EN62477-1, EN60204-1;altitude up to 2000 meters
SAFETY & EMC
SAFETY STANDARDS: UL61010, EN61558-2-16, EAC TP TC 004 approved
WITHSTAND VOLTAGE: I/P-O/P:4.87KVAC I/P-FG:2.4KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE: I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION:
EN61204-3 Conducted: Class B
EN61204-3 Radiated: Class B
EN61000-3-2 Harmonic Current: Class A
EN61000-3-3 Voltage Flicker
EMC IMMUNITY:
EN55024 , EN61204-3
EN61000-4-2 ESD: Level 4, 15KV air ; Level 4, 8KV contact
EN61000-4-3 Radiated Susceptibility: Level 3
EN61000-4-4 EFT/Burest: Level 3
EN61000-4-5 Surge: Level 4, 2KV / Line-Line, Level 4, 4KV/ Line-Earth
EN61000-4-6 Conducted: Level 3
EN61000-4-8 Magnetic Field: Level 4
EN61000-4-11 Voltage Dips and interruptions: >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
MTBF: 515.4K hrs min. Telcordia SR-332(Bellcore); 215.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSIONS: (WxHxD) 63 x 125.2 x 113.5 mm